HETROC RECOVERY CYLINDER 50L ( SUITABLE FOR R22,R410)

Category: Brand:

Description

User Manual

1. Cylinder Structure

  • The refrigerant recovery cylinder consists of a sealed tank body and angle valves.
  • The blue angle valve is the pressurizing valve: refrigerant recovery is connected through the blue valve.
  • The red angle valve is the pressure relief valve: refrigerant filling and tank evacuation are connected through the red valve.

2. Cylinder Evacuation

The cylinder remains sealed during refrigerant recovery. Air trapped inside the tank cannot be vented and will be compressed, which may trigger the safety relief valve even before reaching the rated working pressure.

Before recovering refrigerant, connect a vacuum pump to the red angle valve of the cylinder for evacuation. Open only the red valve and close all other valves during pumping. Perform full vacuum evacuation to eliminate residual air and moisture inside the tank.

3. Cylinder Heating During Recovery

  • The cylinder will heat up during refrigerant recovery.
  • This is a normal physical phenomenon: refrigerant vapor condenses into liquid under pressure and releases latent heat.
  • Simply cool the tank: Pour cold water over the cylinder or submerge it in a large bucket of cold water.

4. Refrigerant Filling Capacity

  • The recovered refrigerant charge shall not exceed 80% of the cylinder’s rated capacity. Excessive filling will automatically pop the safety relief valve.
  • Example: A 50kg-rated recovery cylinder can hold a maximum of 40kg of refrigerant, and must not exceed this limit.

5. R32 Refrigerant Filling

For R32 refrigerants, the filling capacity shall be controlled within 70% of the cylinder rated volume. Cylinders shall be dedicated to a single refrigerant type. Cylinders previously filled with R22 or R410 shall not be used to recover R32. Residual contaminants will increase fire and explosion hazards.

Important Warnings

  1. Do not adjust the safety relief valve by yourself! Any leakage or malfunction caused by unauthorized adjustment of the safety valve voids the product warranty.
  2. Any instance where the cylinder safety relief valve releases pressure as a result of failing to perform vacuum evacuation before cylinder operation shall be excluded from warranty coverage.
  3. Warranty is void if the safety valve pops from overfilling beyond 80% of the cylinder’s rated capacity.
  4. Warranty is void for tank damage or gas leakage caused by human error or external impact.
Specification50 lbs / 22.7 L110 lbs / 50 L
Refrigerant capacity50lbs/22.7L110lbs/50L
Gas tightness test pressure2.5MPA3.9MPA
RefrigerantR12 R22 R134 R410 etcR12 R22 R134 R410 etc
Work pressure20KG33KG
Safety valve pressure33KG33KG
Thickness2.75mm6mm
Main steel plateHp295Hp295